Computational Fluid Dynamics (CFD) simulation inside an Operation Theatre (OT), considering real world conditions such as temperature and airflow movement in the OT environment is carried out. Simulation is carried out using Phoenics software to predict the flow velocity and temperature distribution inside the OT. Parametric study is done to determine the most suitable inlet and outlet configuration. Only one out of the six cases provided the required cooling and reduced recirculation. Results indicated that the entire ceiling inlet with eight outlets was the best case, for further studies to be carried out considering contaminants.

Downloads

Download data is not yet available.

Downloads

Published

2018-04-15

How to Cite

Muneera Abs Farj, Syed Mohammed Aminuddin Aftab, & Kamarul Arifin Ahmad. (2018). Parametric Study to Determine Optimum HVAC in a Hospital Operation Theatre. Journal of Advanced Research in Fluid Mechanics and Thermal Sciences, 44(1), 99–122. Retrieved from https://semarakilmu.com.my/journals/index.php/fluid_mechanics_thermal_sciences/article/view/2700