Parametric Study to Determine Optimum HVAC in a Hospital Operation Theatre

Authors

  • Muneera Abs Farj Department of Aerospace Engineering, Universiti Putra Malaysia, Selangor, 43400, Malaysia
  • Syed Mohammed Aminuddin Aftab Aero Mechanical Department, Abu Dhabi Polytechnic, Al Ain, P.O. Box 66844, UAE
  • Kamarul Arifin Ahmad Department of Mechanical Engineering, College of Engineering, King Saud University, P.O. Box 800, Riyadh 11421, Saudi Arabia

Keywords:

Operation Theatre (OT), Computational Fluid Dynamics (CFD), Heat Ventilation and Air Conditioning (HVAC), Phoenics

Abstract

Computational Fluid Dynamics (CFD) simulation inside an Operation Theatre (OT), considering real world conditions such as temperature and airflow movement in the OT environment is carried out. Simulation is carried out using Phoenics software to predict the flow velocity and temperature distribution inside the OT. Parametric study is done to determine the most suitable inlet and outlet configuration. Only one out of the six cases provided the required cooling and reduced recirculation. Results indicated that the entire ceiling inlet with eight outlets was the best case, for further studies to be carried out considering contaminants.

Downloads

Download data is not yet available.

Downloads

Published

2018-04-15

How to Cite

Muneera Abs Farj, Syed Mohammed Aminuddin Aftab, & Kamarul Arifin Ahmad. (2018). Parametric Study to Determine Optimum HVAC in a Hospital Operation Theatre. Journal of Advanced Research in Fluid Mechanics and Thermal Sciences, 44(1), 99–122. Retrieved from https://semarakilmu.com.my/journals/index.php/fluid_mechanics_thermal_sciences/article/view/2700

Issue

Section

Articles

Most read articles by the same author(s)

1 2 > >>